Current Position:Home->Product Infomation  
DW45 Intelligent conventional breaker
www.chinasonor.com  2014/10/20  
  

DW45 Series intelligent conventional breaker Application:

DW45 series intelligent breaker is applicable in the distribution network of AC 50Hz, rated voltage of 400V 

and 690Vand rated current from 630A~3200A, to distribute electric energy protection circuit and prevent 

power equipments from harm of overload, under-voltage, short circuit and single-phase earthing etc. 

Provided with intelligent protecting function and precise selective protection, breaker can enhance 

the dependability of power supply and avoid the unexpected power cut. 

This product accords with the standard of IEC60947-2.

Working and installation condition

Installation mode:fixed type, drawable type.

Operation mode:motor operated, manually operated(for serving).

Pole number:three pole, four pole.

Release type:intelligent type over-current controller,under-voltage instantaneous(or time-delay) operation release:shunt release.

The properties of intelligent type over-current controller:

a.Long time delay over-current protection inverse time limit, short time delay over-current protection inverse time limited, short time delay over current protection fixed time limit, instantaneous.

b.Single-phase earthing protection function.

c.Presenting function:setting current lr,action current, setting time, action time.

d.Alarming function:overload alarming

e.Self-checking function:over-heat protection,microcomputer self diagnosing.

f.Testing function

g.Load monitoring function.

h.Thermal simulation function.

i.MCR function.

j.Fault memory function.

Ambient Temperature:

a.Temperature:40T5 average value for 24 hours35

Note:working condition of minimum temperature is -10 or -25, users must declare while ordering;

Working condition of maximum temperature exceed 40 or minimum temperature under -25,the users should consult with our factory.

b.Altitude:2000m.

c.Air relative humidity:50%, when the max temperature is 40 and can be more while the temperature is lower, monthly average temperature in the most humid month 25,monthly average maximum relative humidity 90%.

d.Pollution grade:3.

e.Installation type: the type of circuit breaker, main circuit, under-voltage tripping coil and supply transformer is IV,the type of other ancillary circuit,controlling circuit is.

F. Installation condition:installation of circuit breaker shall accord to the instruction,and the vertical gradient of  installation place should not exceed 5°.

 

Drawing:


Accessories:


Specification:


Package and Pictures:



 
 
YUEQING SONOR GROUP
ADD:Yueqing city, Zhejiang, China P.C:325603 E-MAIL:sale@chinasonor.com
TEL: 86-577-62873250 MOB: 86-18066287511 FAX: 86-577- MSN: happy2817
Copyright © 2009 www.chinasonor.com All Rights Reserved.  Technique Support:wzmywl.com