Current Position:Home->Product Infomation  
GV Motor Protection Circuit Breaker
www.chinasonor.com  2014/5/16  
  

1

1.Application

GV series motor protection circuit breaker are mainly used fo the overload and short circuit protection of the motor in AC 50/60Hz, up to 660V, 0.1-80A power circuit, as a full-voltage starter to start and cut off the motor, under the AC3 load or for the overload and short circuit protection of the circuit and power equipment in the power distribution network.

2.Specification

Type Standard power ratings of 3-phase motors 50/60Hz in category AC-3 Current setting range (A)
220V 380V 415V 440V 500V 660V
kW kW kW kW kW kW
GV1-M01 - - - - - - 0.1-0.16
GV1-M02 - - - - - - 0.16-0.25
GV1-M03 - - - - - - 0.25-04
GV1-M04 - - - - - 0.37 0.4-0.63
GV1-M05 - - - 0.37 0.37 0.55 0.63-1
GV1-M06 - 0.37 - 0.55 0.75 1.1 1-1.6
GV1-M07 0.37 0.75 1.1 1.1 1.1 1.5 1.6-2.5
GV1-M08 0.75 1.5 1.5 1.5 2.2 3 2.5-4
GV1-M10 1.1 2.2 2.2 3 3.7 4 4-6
GV1-M14 2.2 4 4 4 5.5 7.5 6-10
GV1-M20 4 7.5 7.5 7.5 10 11 10-16
GV1-M21 5.5 10 9 9 11 15 16-20
GV1-M22 5.5 11 11 11 15 18.5 20-25
GV2-M32 7.5 15 15 15 18.5 26 24-32
GV3-M25 5.5 11 11 11 15 18.5 16-25
GV3-M40 11 18.5 22 22 25 33 25-40
GV3-M63 15 30 33 33 40 55 40-63
GV3-M80 22 40 45 45 55 63 56-80
 
 
YUEQING SONOR GROUP
ADD:Yueqing city, Zhejiang, China P.C:325603 E-MAIL:sale@chinasonor.com
TEL: 86-577-62873250 MOB: 86-18066287511 FAX: 86-577- MSN: happy2817
Copyright © 2009 www.chinasonor.com All Rights Reserved.  Technique Support:wzmywl.com
浙ICP备14013461号-1